Applications

UPS & Data Centre Batteries

15 mintypical discharge to 1.67 V/cell
2.27–2.30 Vfloat voltage per cell at 25 °C
+10 °Croughly halves float life

A UPS battery is sized in watts per cell for a fixed runtime, not in amp-hours. That one difference is where most tenders go wrong: a 100 Ah block that looks generous at the C20 rate may deliver a fraction of that at 15 minutes to 1.67 V per cell. We build high-rate AGM blocks and tubular VRLA cells for server rooms, switchgear, substations and containerised data halls, from 12 V 7 Ah wall units to 2 V 3000 Ah rack strings.

What decides life in this duty

Power per cell beats amp-hours

Ask for the watt figure at your real runtime: 15 minutes for most UPS, 5 to 10 for switchgear. Compare quotes at the same end voltage, because a 1.75 V cut-off flatters the number and shortens the backup you actually get.

Ripple and float voltage quietly cook the block

Charger ripple above roughly 2% RMS raises internal temperature without moving the room thermometer. Hold float at 2.27–2.30 V per cell at 25 °C, and measure at the battery terminals, not at the charger panel.

End of life shows up as resistance first

Grid corrosion and electrolyte dry-out push internal resistance up long before capacity collapses. An annual impedance trend catches the weak block while a full discharge test would still pass it.

What to put in the RFQ

  • Runtime and end voltage, e.g. 15 min to 1.67 V/cell
  • Load in kW today, plus expansion margin
  • Ambient temperature inside the cabinet or room
  • Rack dimensions and front or rear service access
  • Design life target: 5, 10 or 15+ years

Series built for this duty

Pulled from the catalogue by application tag, not by marketing copy. Every series below is engineered for this load profile.

Buyer questions

Can I fit a larger Ah block for more runtime?

Only if the footprint, terminal layout and charger recharge current all still work. A bigger block on an undersized charger recharges slowly and sits at partial charge between outages, which is where most premature capacity loss starts.

AGM or tubular gel for a data centre?

AGM for short runtime, sealed cabinets and the lowest cost per kW. Tubular gel (OPzV) where the target is 15 to 20 years of design life, deeper cycling or high ambient temperature, since it tolerates both better at a higher price per kWh.

How often should a string be discharge tested?

An acceptance test at commissioning, an annual impedance or conductance check, and a full capacity test every three to five years, or sooner once impedance drifts more than about 20% from the commissioning baseline.

Read before you quote

Send us the load profile

Tell us the voltage, runtime or days of autonomy, ambient temperature and target design life. We reply with a sized recommendation and an FOB price, usually within one working day.

Request a quote →