The Battery Died at Month 13. Prove It Wasn't the Charger.
A distributor sent a photo instead of a claim form: a 12V block with a bulged case, 13 months old. The page that decides who pays should have been written before installation.

A photo is not a claim
Last month a distributor in Poland sent me a picture instead of a claim form. A 12V 200Ah AGM block, case bulged along the long side, positive post a little shiny where it had got hot. The message was four words: "13 months. Warranty?"
I asked three things back. What was the float voltage? What was the cabinet temperature in July? Do you still have the commissioning sheet? He answered one of them: "It sits in a telecom cabinet, nobody touches it."
That last sentence is usually where these stories end. Not because the battery is innocent, but because after thirteen months nobody can prove anything either way — and the side that cannot prove anything loses.
A warranty is not a promise that the battery will not fail
This is the part that gets lost in translation between a factory and an importer. A warranty covers a manufacturing defect. It does not cover a battery that was asked to do something it was never designed for. Both show up as "dead battery at month 13", and they look identical from the outside.
Four failure modes account for almost everything I see coming back:
| What you see | What usually caused it | Covered? |
|---|---|---|
| Case bulged, posts discoloured, acid smell | Overcharge. Float above 13.8 V at 25 °C, no temperature compensation, dried-out separator | No |
| Capacity fades gradually, rests at 12.2–12.4 V, never fully recharges | Chronic undercharge. Float below 13.4 V, loose connections, undersized charger | No |
| One block at 0–10.5 V, the rest of the string fine | Internal short, usually a manufacturing defect or a plate damaged in handling | Yes, if you can show the rest were healthy |
| Whole string at 10.5 V after a long outage | Deep discharge beyond the design DoD, then left flat for weeks | No |
Only one row in that table is the factory's problem. The other three are installation problems — and they account for most of the returns I hear about in this industry, not just ours.
The 10 °C rule decides more claims than any inspection
Lead-acid design life is quoted at 25 °C. Move the same battery to 35 °C and the chemical reaction rate roughly doubles; you get about half the years. At 45 °C you are down to a quarter. This is the Arrhenius relationship, and it is not marketing — it is why telecom and UPS rooms are air-conditioned and why a battery room that "works fine" in Europe falls apart in the Middle East.
So a block rated 10 years at 25 °C, sitting in an uncooled cabinet that hits 38 °C every afternoon, is a 5-year battery at best. If it dies at month 13, that is not a defect. It is a mismatch between the product and the site, and it was decided the day the cabinet was specified, long before anyone thought about the battery.
Does that mean the supplier is always right? No. I have seen genuine defects — a bad weld inside a block, a separator folded during assembly, a batch with the wrong acid density. But those fail early, usually inside the first three months, and they fail in a recognisable pattern. A failure at month 13 with a normal-looking case is almost always a charging story.
The one page that decides the argument
Before the first block goes in, spend twenty minutes filling in a commissioning sheet. Not for the supplier's benefit — for yours.
- Date of installation and the ambient temperature at the time.
- Open-circuit voltage of every block, recorded individually. Not the string voltage.
- Torque value used on the terminals, and the wrench setting.
- Charger make, model, and the actual measured float voltage at the terminals — measured with a meter, not read off the display.
- A photo of the cabinet, the wiring, and the serial labels.
One page. Ten minutes. It is the difference between a claim and an argument.
Then keep a light log: cabinet temperature once a month (a €15 USB logger does this better than a person), any mains outage longer than an hour, and the float current if the charger shows it. When a block does fail, you can answer the only two questions that matter — was it charged correctly, and was it too hot — with numbers instead of opinion.
You can find the float-voltage settings we recommend, and why 2.27 V per cell is a temperature rather than a number, in our note on temperature compensation. If the battery has been sitting at partial charge for months, the failure has a name, and it is not "old age" — it is sulphation, which we wrote about here.
How a claim actually gets paid
A warranty claim is not a complaint. It is a file. The ones that get settled without a fight usually contain:
- Model, serial number, quantity, invoice date, installation date.
- Per-block OCV, measured and written down, with the meter model.
- A load test: instrument, load current, duration, end voltage.
- Charger output measured at the battery terminals under load.
- Temperature history, even if it is just a monthly handwritten number.
- Photos: the block, the terminals, the label, the cabinet.
- A clear ask — replacement, credit, or a root-cause report.
Missing item 2 or 4 and the supplier will ask for them, which costs you another two weeks and a container sitting at the port. Missing both, and the claim quietly dies.
Pro-rata is simpler than people fear. If the warranty is 24 months pro-rata and the block fails in month 13, the credit is roughly (24 − 13) / 24, so a bit under half. If it is a free-replacement warranty for the first 12 months, month 13 is already past the line — which is exactly why the installation date matters more than the shipping date.
What I would change in the next purchase order
Three lines, no extra cost:
- Require a commissioning sheet as part of the delivery documents. If the supplier does not have a template, send yours.
- Specify the float voltage at 25 °C and require a temperature-compensated charger. Not "suitable charger" — a number and a compensation slope.
- Ask which standard the float life is quoted against, and at what temperature. A 10-year claim with no temperature attached is a brochure, not a specification.
The battery that failed in Poland was probably overcharged for a year in a cabinet nobody opened. The replacement will do the same thing unless the charger is set correctly. That is the uncomfortable part of this job: the second failure is usually the one you could have prevented.
Sources
Discover Battery, "How to store VRLA batteries," technical note, accessed 27 Nov. 2026, http://www.discoverbatterys.com/newsdetail_3172387.html.
Sebang Battery, "How to store valve-regulated lead-acid batteries," technical note, 12 June 2023, http://www.orzxyx.com/news/303.html.
Exisde Power, "Effect of operating temperature and temperature compensation on lead-acid batteries," technical note, accessed 27 Nov. 2026, http://www.exisde.cn/?gongsi/599.html.
Shandong Sacred Sun Power Sources, "Core mechanisms of premature ageing in room lead-acid batteries," technical note, accessed 27 Nov. 2026, http://sdtrojan.com/?hangye/119.html.